NSN 5925-00-248-1403 1764769, 00-248-1403, 002481403
Product Details | CIRCUIT BREAKER TRIPPER
5925-00-248-1403 An electromechanical device which releases the holding mechanism and permits the contacts of a circuit breaker to open. It is a replacement part of a circuit breaker. Does not include relays. See also THERMAL RELEASE, CIRCUIT BREAKER.
Part Alternates: 1764769, 5925-00-248-1403, 00-248-1403, 5925002481403, 002481403
Electrical and Electronic Equipment Components | Circuit Breakers
| Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 59 | 00-248-1403 | 04558 ( TRIPPER, CIRCUIT BREAKER ) |
Request a Quote
What Our Customers Say
Compare
NSNs for Compare ( up to 4 ): Add 5925-00-248-1403
Related Products | NSN 5925-00-248-1403
Technical Data | NSN 5925-00-248-1403
| Characteristic | Specifications |
|---|---|
| POLE QUANTITY | 3 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 250.0 AMPERES AC AND 250.0 AMPERES DC ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC AND 250.0 DC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5400.000 NOMINAL AT 150 PCT AND 600.000 MINIMUM AT 200 PCT AND 1440.000 MAXIMUM AT 200 PCT AND 120.000 MINIMUM AT 300 PCT AND 450.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 ALL LOCATIONS |
| BODY STYLE | 1D RECTANGULAR DIMENSIONAL ENVELOPE |
| OVERALL LENGTH | 7.750 INCHES NOMINAL |
| OVERALL HEIGHT | 4.250 INCHES NOMINAL |
| OVERALL WIDTH | 4.750 INCHES NOMINAL |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 TERMINAL |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | 1500.0 TO 1750.0 AC AND 1500.0 TO 1750.0 DC ALL LOCATIONS |
| MANUFACTURERS CODE | 79500 |
| DESIGN CONTROL REFERENCE | 1764769 |
Restrictions/Controls & Freight Information | NSN 5925-00-248-1403
| Category | Code | Description |
|---|---|---|
| Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
| Category | Code | Description |
|---|---|---|
| No Freight Information | ||