NSN 5925-00-462-5506 M39019/4-40, M39019440, MILC390194
Product Details | CIRCUIT BREAKER
5925-00-462-5506 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: M39019/4-40, M39019440, MILC390194, MILC39019-4, 352250009234, 5925-00-462-5506, 00-462-5506, 5925004625506, 004625506
Electrical and Electronic Equipment Components | Circuit Breakers
| Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 59 | 30 MAY 1974 | 00-462-5506 | 00136 ( CIRCUIT BREAKER ) |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-00-462-5506
Technical Data | NSN 5925-00-462-5506
| Characteristic | Specifications |
|---|---|
| POLE QUANTITY | 2 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 3.0 AMPERES AC ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.500 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 60.000 MAXIMUM ALL LOCATIONS |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY STYLE | 1B MULTIPOLE-SINGLE ACTUATOR TYPE |
| BUSHING LENGTH | 0.330 INCHES NOMINAL |
| BODY LENGTH | 1.562 INCHES MAXIMUM |
| BODY WIDTH | 1.281 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.906 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.828 INCHES MAXIMUM |
| CASE MATERIAL | METAL |
| MOUNTING FACILITY TYPE AND QUANTITY | THD BUSHING W/PANEL SEAL |
| THREAD SERIES DESIGNATOR | UNEF |
| NOMINAL THREAD SIZE | 0.375 INCHES |
| THREAD QUANTITY PER INCH | 32 |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| TERMINAL TYPE AND QUANTITY | 4 WIRE HOOK |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE TWO |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 0.5 AC AND 0.5 DC |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 120.0 AC AND 50.0 DC |
| SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| TEST DATA DOCUMENT | 81349-MIL39019/4 SPECIFICATION |
| III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| MANUFACTURERS CODE | 81349 |
| NON-DEFINITIVE GOVERNMENT SPEC/STD REFERENCE | MILC39019-4 |
| MANUFACTURERS CODE | 81349 |
Restrictions/Controls & Freight Information | NSN 5925-00-462-5506
| Category | Code | Description |
|---|---|---|
| Shelf-Life Code: | 0 | Nondeteriorative |
| Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
| Demilitarization Code: | A | Non-Munitions List Item/ Non-Strategic List Item - Demilitarization not required. |
| Controlled Inventory Item Code: | U | UNCLASSIFIED |
| Precious Metals Indicator Code: | A | Item does not contain precious metal |
| Criticality Code: | X | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
| Category | Code | Description |
|---|---|---|
| No Freight Information | ||
Management | NSN 5925-00-462-5506
| Category | Code | Description |
|---|---|---|
| Cognizance Codes | 9N | Navy-owned stocks of defense electronic material Naval Inventory Control Point, Mechanicsburg |
| Source of Supply | S9E | Defense Supply Center Columbus Columbus, OH 43218 |
| Agency | DN | Department of the Navy |
| Service Organization | N | U.S. Navy |
| Acquisition Advice Codes | Y | TERMINAL ITEM #(NON-STOCKED ITEMS) Future procurement is not authorized. No wholesale stock is available for issue. 1. Requisitions will not be processed to the wholesale manager. 2. Internal Service/agency requisitioning may be continued in accordance with the Service/agency requisitioning policies. |
| Controlled Item Code | U | UNCLASSIFIED |
| Shelf Life Code | 0 | Nondeteriorative |