5925-00-533-1426 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: TEB122015, 5925-00-533-1426, 00-533-1426, 5925005331426, 005331426
Electrical and Electronic Equipment Components | Circuit Breakers
| Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 59 | 11 SEP 1974 | 00-533-1426 | 00136 ( CIRCUIT BREAKER ) |
Cross Reference | NSN 5925-00-533-1426
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| TEB122015 | 60969 | GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-00-533-1426
Technical Data | NSN 5925-00-533-1426
| Characteristic | Specifications |
|---|---|
| POLE QUANTITY | 2 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC AND 10.0 AMPERES DC ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 250.0 DC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| TRIP RELEASE DUTY CYCLE | CONTINUOUS ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 65.000 MINIMUM AT 150 PCT AND 400.000 MAXIMUM AT 150 PCT ALL LOCATIONS |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY STYLE | 13B MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY LENGTH | 6.312 INCHES NOMINAL |
| BODY WIDTH | 2.750 INCHES NOMINAL |
| BODY HEIGHT | 3.812 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.874 INCHES NOMINAL |
| CASE MATERIAL | PLASTIC |
| MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP-RESET |
| ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO AND BETWEEN POLE THREE AND FOUR |
| TERMINAL TYPE AND QUANTITY | 4 SCREW |
Restrictions/Controls & Freight Information | NSN 5925-00-533-1426
| Category | Code | Description |
|---|---|---|
| Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
| Demilitarization Code: | A | Non-Munitions List Item/ Non-Strategic List Item - Demilitarization not required. |
| Precious Metals Indicator Code: | U | Precious metal type is unknown |
| Criticality Code: | X | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
| Category | Code | Description |
|---|---|---|