Product Details | CIRCUIT BREAKER

5925-00-975-0975 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: TRP1120, 5925-00-975-0975, 00-975-0975, 5925009750975, 009750975

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 01 JAN 1962 00-975-0975

Cross Reference | NSN 5925-00-975-0975

Part Number Cage Code Manufacturer
TRP1120 24446 GENERAL ELECTRIC CO

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-00-975-0975

Technical Data | NSN 5925-00-975-0975

Characteristic Specifications
POLE QUANTITY 1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 20.0 AMPERES AC SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 120.0 AC SINGLE LOCATION
FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC SINGLE LOCATION
CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
TRIP RELEASE METHOD THERMAL-MAGNETIC SINGLE LOCATION
TRIP RELEASE DUTY CYCLE CONTINUOUS SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 90.000 MINIMUM AT 150 PCT AND 200.000 MAXIMUM AT 150 PCT AND 30.000 MINIMUM AT 200 PCT AND 55.000 MAXIMUM AT 200 PCT AND 14.000 MINIMUM AT 300 PCT AND 26.000 MAXIMUM AT 300 PCT AND 8.000 MINIMUM AT 400 PCT AND 14.000 MAXIMUM AT 400 PCT AND 5.000 MINIMUM AT 500 PCT AND 9.000 MAXIMUM AT 500 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 SINGLE LOCATION
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
OVERALL LENGTH 2.843 INCHES NOMINAL
OVERALL HEIGHT 2.921 INCHES NOMINAL
OVERALL WIDTH 0.968 INCHES NOMINAL
CASE MATERIAL PLASTIC
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT POLE ONE
TERMINAL TYPE AND QUANTITY 1 SCREW AND 1 QUICK DISCONNECT, MALE
SPECIAL FEATURES MOUNTING TYPE IS TERMINAL
III ARC QUENCHING METHOD DEION
MANUFACTURERS CODE 24446
DESIGN CONTROL REFERENCE TRP1120

Restrictions/Controls & Freight Information | NSN 5925-00-975-0975

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Precious Metals Indicator Code:UPrecious metal type is unknown
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Category Code Description
No Freight Information