Product Details | CIRCUIT BREAKER

5925-01-084-2946 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: AM1516MG315125VACC3, AM1516MG3-15-125VACC3, 5925-01-084-2946, 01-084-2946, 5925010842946, 010842946

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 15 OCT 1979 01-084-2946

Drawings & Photos | NSN 5925-01-084-2946


Cross Reference | NSN 5925-01-084-2946

Part Number Cage Code Manufacturer
AM1516MG3-15-125VACC3 74193 EATON CORP HEINEMANN PRODUCTS

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-084-2946

Technical Data | NSN 5925-01-084-2946

Characteristic Specifications
POLE QUANTITY 1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES AC SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 125.0 AC SINGLE LOCATION
FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 2000.0 AC SINGLE LOCATION
TRIP RELEASE METHOD MAGNETIC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 4.000 NOMINAL AT 100 PCT AND 1.000 NOMINAL AT 125 PCT AND 0.300 NOMINAL AT 150 PCT AND 0.150 NOMINAL AT 200 PCT AND 0.030 NOMINAL AT 400 PCT AND 0.020 NOMINAL AT 500 PCT AND 0.003 NOMINAL AT 1000 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 SINGLE LOCATION
RESET METHOD MANUAL
BODY STYLE 12A SINGLE POLE TYPE
BODY LENGTH 3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM
BODY WIDTH 0.980 INCHES MINIMUM AND 1.000 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 3.053 INCHES MINIMUM AND 3.073 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
BOSS HEIGHT 0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE 3.167 INCHES MINIMUM AND 3.311 INCHES MAXIMUM
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED HOLE
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE 0.138 INCHES
THREAD QUANTITY PER INCH 32
MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
ACTUATOR POSITION DESIGNATION AT POLE ONE
TERMINAL TYPE AND QUANTITY 2 THREADED STUD
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
III ARC QUENCHING METHOD MAGNETIC BLOWOUT

Restrictions/Controls & Freight Information | NSN 5925-01-084-2946

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Precious Metals Indicator Code:UPrecious metal type is unknown
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Category Code Description
No Freight Information