5925-01-103-6045 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: AM333MG6515, AM333MG6-5-15, GC885E14A, 5925-01-103-6045, 01-103-6045, 5925011036045, 011036045

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 01-103-6045

Drawings & Photos | NSN 5925-01-103-6045


Cross Reference | NSN 5925-01-103-6045

Part Number Cage Code Manufacturer
711570-149 05869 RAYTHEON COMPANY DBA RAYTHEON
711570-149 82577 RAYTHEON COMPANY DBA RAYTHEON
72-126-6MG6 74193 EATON CORP HEINEMANN PRODUCTS
AM3-C3-5-2 74193 EATON CORP HEINEMANN PRODUCTS
AM333-15-250-15-400 74193 EATON CORP HEINEMANN PRODUCTS
AM333MG6-5-15 74193 EATON CORP HEINEMANN PRODUCTS
APL-111-1-42-502-M 81541 SENSATA TECHNOLOGIES MARYLAND, INC
APL-111-55629/5-047 81541 SENSATA TECHNOLOGIES MARYLAND, INC
GC885E14A 26512 NORTHROP GRUMMAN SYSTEMS CORPORATION DIV NORTHROP GRUMMAN AEROSPACE
LAM333-5-250-400 36378 RAYTHEON TECHNICAL SERVICES COMPANY
M55629/5-047 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY
MIL-C-55629/5 81349 MILITARY SPECIFICATIONS PROMULGATED BY MILITARY
W93X13-2-5 77342 TYCO ELECTRONICS CORPORATION

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-103-6045

Technical Data | NSN 5925-01-103-6045

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 5.0 AMPERES AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 AC ALL LOCATIONS
FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC ALL LOCATIONS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 1.250 MINIMUM AT 200 PCT AND 9.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 8C MULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY LENGTH 2.500 INCHES NOMINAL
BODY WIDTH 2.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.940 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.062 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.750 INCHES NOMINAL
BOSS HEIGHT 0.140 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE 2.471 INCHES NOMINAL
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE 0.138 INCHES
THREAD QUANTITY PER INCH 32
MANUAL ACTUATOR TYPE AND QUANTITY 3 TOGGLE
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, AND THREE LINKED
TERMINAL TYPE AND QUANTITY 6 THREADED STUD
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED GENERAL PURPOSE
III STORAGE TYPE GENERAL PURPOSE WAREHOUSE