Product Details | CIRCUIT BREAKER

5925-01-166-7118 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: 5189636006, 5189636-006, 6752-322-40, 5925-01-166-7118, 01-166-7118, 5925011667118, 011667118, 675232240

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 16 NOV 1983 01-166-7118

Drawings & Photos | NSN 5925-01-166-7118


Demand History | NSN 5925-01-166-7118

Part Number Request Date QTY Origin
5925-01-166-7118 2018-05-135 9 DIBBS

Cross Reference | NSN 5925-01-166-7118

Part Number Cage Code Manufacturer
5189636-006 15090 RAYTHEON COMPANY DBA RAYTHEON
5189636-006 53711 NAVAL SEA SYSTEMS COMMAND
6752-322-40 82647 SENSATA TECHNOLOGIES, INC DIV SENSATA ATTLEBORO

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-166-7118

Technical Data | NSN 5925-01-166-7118

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 40.0 AMPERES AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 120.0 AC ALL LOCATIONS
FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 6000.0 AC SINGLE LOCATION
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 18.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 140.0 ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 4B MULTIPOLE-SINGLE ACTUATOR TYPE
BUSHING LENGTH 0.145 INCHES MINIMUM AND 0.155 INCHES MAXIMUM
BODY LENGTH 2.200 INCHES MAXIMUM
BODY WIDTH 2.270 INCHES MAXIMUM
BODY HEIGHT 2.470 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.190 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.500 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.810 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.750 INCHES NOMINAL
CASE MATERIAL PLASTIC
MOUNTING FACILITY TYPE AND QUANTITY 6 THREADED HOLE
THREAD SERIES DESIGNATOR UNC
NOMINAL THREAD SIZE 0.138 INCHES
THREAD QUANTITY PER INCH 32
MANUAL ACTUATOR TYPE AND QUANTITY 1 PUSH-PULL
ACTUATOR FUNCTION TRIP-RESET
ACTUATOR POSITION DESIGNATION AT POLE TWO
TERMINAL TYPE AND QUANTITY 6 TAB W/SCREW
AUXILIARY SWITCH FUNCTION AND QUANTITY 1 ALARM
SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE ONE
SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED SHOCK RESISTANT AND DUSTTIGHT AND SAND RESISTANT AND CORROSION RESISTANT AND EXPLOSION PROOF
III ARC QUENCHING METHOD MAGNETIC BLOWOUT
III STORAGE TYPE GENERAL PURPOSE WAREHOUSE
III SPECIAL HANDLING FEATURE MAGNETIC

Restrictions/Controls & Freight Information | NSN 5925-01-166-7118

Category Code Description
Shelf-Life Code:0Nondeteriorative
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Controlled Inventory Item Code:UUNCLASSIFIED
Precious Metals Indicator Code:AItem does not contain precious metal
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Automatic Data Processing Equipment:0Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)
Category Code Description
NMF Description 061300 CIRCUIT BREAKER/SWITCH NOI
Less than car load rating
Less than truck load rating P 77.5
Water commodity Code 658 unknown
Originating Activity Code HD Naval Inventory Control Point
Mechanicsburg, PA 17055-0788
Air Dimension Code A Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Air Commodity H Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
Air Special Handling Z No special handling required.
Special Handling Code 9 unknonwn
HAZMAT
Type of Cargo Z No special type of cargo code applicable

Management | NSN 5925-01-166-7118

Category Code Description
Cognizance Codes9BNavy-owned stocks of DLA material
Naval Inventory Control Point, Mechanicsburg
Source of SupplySMSDefense Logistics Agency
Enterprise Business Systems
AgencyDNDepartment of the Navy
Service OrganizationNU.S. Navy
Acquisition Advice CodesZINSURANCE/NUMERIC STOCKAGE OBJECTIVE ITEM # Items which may be required occasionally or intermittently, and prudence requires that a nominal quantity of materiel be stocked due to the essentiality or the lead time of the item. 1. The item is centrally managed, stocked, and issued. 2. Requisitions will be submitted in accordance with IMM/Service requisitioning procedures.
Controlled Item CodeUUNCLASSIFIED
Shelf Life Code0Nondeteriorative
Purchasing QTY
UOM
1
EA : Each