NSN 5925-01-483-0111 IEG6-1REC4-61-15.0-21-V, IEG61REC46115021V, 01-483-0111
Product Details | CIRCUIT BREAKER
5925-01-483-0111 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: IEG6-1REC4-61-15.0-21-V, IEG61REC46115021V, 5925-01-483-0111, 01-483-0111, 5925014830111, 014830111
Electrical and Electronic Equipment Components | Circuit Breakers
| Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 59 | 13 MAR 2001 | 01-483-0111 | 00136 ( CIRCUIT BREAKER ) |
Cross Reference | NSN 5925-01-483-0111
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| IEG6-1REC4-61-15.0-21-V | 81541 | SENSATA TECHNOLOGIES MARYLAND, INC |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-01-483-0111
Technical Data | NSN 5925-01-483-0111
| Characteristic | Specifications |
|---|---|
| POLE QUANTITY | 1 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES/RELAY TRIP ALL LOCATIONS |
| AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 125.0 AC NOMINAL ALL LOCATIONS |
| TRIP RELEASE DUTY CYCLE | CONTINUOUS ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.700 MINIMUM AT 125 PCT AND 12.000 MAXIMUM AT 125 PCT AND 0.350 MINIMUM AT 150 PCT AND 7.000 MAXIMUM AT 150 PCT AND 0.130 MINIMUM AT 200 PCT AND 3.000 MAXIMUM AT 200 PCT AND 0.030 MINIMUM AT 400 PCT AND 1.000 MAXIMUM AT 400 PCT AND 0.015 MINIMUM AT 600 PCT AND 0.300 MAXIMUM AT 600 PCT AND 0.010 MINIMUM AT 800 PCT AND 0.150 MAXIMUM AT 800 PCT AND 0.008 MINIMUM AT 1000 PCT AND 0.100 MAXIMUM AT 1000 PCT ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| ULTIMATE TRIP TIME PER POLE IN SECONDS | 0.700 MINIMUM AND 12.000 MAXIMUM ALL LOCATIONS |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY STYLE | 4A SINGLE POLE TYPE |
| BODY LENGTH | 2.000 INCHES NOMINAL |
| BODY WIDTH | 0.750 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.530 INCHES NOMINAL |
| TERMINAL TYPE AND QUANTITY | 2 SCREW |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 1.0 AC |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC |
| SWITCH TERMINAL TYPE | QUICK DISCONNECT, MALE |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND MOISTURE RESISTANT AND SALT WATER RESISTANT AND SHOCK RESISTANT AND |
Restrictions/Controls & Freight Information | NSN 5925-01-483-0111
| Category | Code | Description |
|---|---|---|
| Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
| Demilitarization Code: | A | Non-Munitions List Item/ Non-Strategic List Item - Demilitarization not required. |
| Electro-static Discharge Susceptible: | A | No known Electrostatic Discharge (ESD) or Electromagnetic Interference (EMI) sensitivity |
| Precious Metals Indicator Code: | A | Item does not contain precious metal |
| Criticality Code: | X | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
| Automatic Data Processing Equipment: | 0 | Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9) |
| Category | Code | Description |
|---|---|---|
| No Freight Information | ||