5925-01-552-5336 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.

Part Alternates: GH3G3NU001003B, GH3-G3-NU-0010-03B, 5925-01-552-5336, 01-552-5336, 5925015525336, 015525336

Electrical and Electronic Equipment Components | Circuit Breakers

Supply Group (FSG) NSN Assign. NIIN
59 15 JUN 2007 01-552-5336

Drawings & Photos | NSN 5925-01-552-5336


Cross Reference | NSN 5925-01-552-5336

Part Number Cage Code Manufacturer
GH3-G3-NU-0010-03B 1W134 EATON CORP AEROSPACE COMMERCIAL CONTROLS DIV
GH3-G3-NU-0010-03B L3330 HEINEMANN ELECTRIC CANADA INCDIVISION OF EATON CORP

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 5925-01-552-5336

Technical Data | NSN 5925-01-552-5336

Characteristic Specifications
POLE QUANTITY 3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC ALL LOCATIONS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS
FREQUENCY IN HERTZ 50.0 OR 60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC ALL LOCATIONS
CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TRIP RELEASE METHOD MAGNETIC-HYDRAULIC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 0.150 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
RESET METHOD MANUAL
MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
BODY STYLE 11B MULTIPOLE-SINGLE ACTUATOR TYPE
BODY LENGTH 6.000 INCHES NOMINAL
BODY WIDTH 4.125 INCHES NOMINAL
BODY HEIGHT 3.125 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 5.000 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.375 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.687 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.375 INCHES NOMINAL
BOSS HEIGHT 0.250 INCHES NOMINAL
CASE MATERIAL PLASTIC

Restrictions/Controls & Freight Information | NSN 5925-01-552-5336

Category Code Description
Hazardous Material Indicator CodePThere is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product
Demilitarization Code:ANon-Munitions List Item/ Non-Strategic List Item - Demilitarization not required.
Electro-static Discharge Susceptible:ANo known Electrostatic Discharge (ESD) or Electromagnetic Interference (EMI) sensitivity
Precious Metals Indicator Code:AItem does not contain precious metal
Criticality Code:X The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Automatic Data Processing Equipment:0Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)