NSN 5925-01-552-9323 JGE9200AAGF02SNT120CPK, 01-552-9323, 015529323
Product Details | CIRCUIT BREAKER
5925-01-552-9323 A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER.
Part Alternates: JGE9200AAGF02SNT120CPK, 5925-01-552-9323, 01-552-9323, 5925015529323, 015529323
Electrical and Electronic Equipment Components | Circuit Breakers
| Supply Group (FSG) | NSN Assign. | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 59 | 28 JUN 2007 | 01-552-9323 | 00136 ( CIRCUIT BREAKER ) |
Demand History | NSN 5925-01-552-9323
| Part Number | Request Date | QTY | Origin |
|---|---|---|---|
| 5925-01-552-9323 | 2018-05-138 | 4 | us |
Cross Reference | NSN 5925-01-552-9323
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| JGE9200AAGF02SNT120CPK | 55588 | EATON ELECTRICAL INC. DBA CUTTLER HMMER CMRCL CNTRLS DIV |
Request a Quote
What Our Customers Say
Compare
Related Products | NSN 5925-01-552-9323
Technical Data | NSN 5925-01-552-9323
| Characteristic | Specifications |
|---|---|
| POLE QUANTITY | 4 |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 200.0 AMPERES AC AND 200.0 AMPERES DC ALL LOCATIONS |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
| FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 65000.0 AC AND 10000.0 DC ALL LOCATIONS |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
| RESET METHOD | MANUAL |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| BODY STYLE | 11B MULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 5.340 INCHES NOMINAL |
| BODY HEIGHT | 3.440 INCHES NOMINAL |
| CASE MATERIAL | PLASTIC |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| SPECIAL FEATURES | DC RATINGS ARE OF 2-POLES OF 3-POLE CIRCUIT; TRIP UNIT - THERMAL AND MAGNETIC ARE ADJUSTABLE; RATED ULTIMATE BREAKING CAPACITIES - 65000.0 AMPS AT 220.0 TO 240.0 VOLTS AC; 25000.0 AMPS AT 380.0 TO 415.0 VOLTS AC; 25000.0 AMPS AT 480.0 VOLTS AC; 18000.0 AMPS AT 600.0 VOLTS AC; 12000.0 AMPS AT 690.0 VOLTS AC; 10000.0 AMPS AT 250.0 VOLTS DC; OVERALL HEIGHT 7.000 INCHES NOMINAL; INCLUDES FREEZE |
Restrictions/Controls & Freight Information | NSN 5925-01-552-9323
| Category | Code | Description |
|---|---|---|
| Hazardous Material Indicator Code | P | There is no information in the HMIS; however, the NSN is in an FSC in Table II of Federal Standard 313 and an MSDS may be required by the user. The requirement for an MSDS is dependent on a hazard determination of the supplier or the intended end use of the product |
| Demilitarization Code: | A | Non-Munitions List Item/ Non-Strategic List Item - Demilitarization not required. |
| Electro-static Discharge Susceptible: | A | No known Electrostatic Discharge (ESD) or Electromagnetic Interference (EMI) sensitivity |
| Precious Metals Indicator Code: | A | Item does not contain precious metal |
| Criticality Code: | X | The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. |
| Automatic Data Processing Equipment: | 0 | Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9) |
| Category | Code | Description |
|---|---|---|
| No Freight Information | ||