Product Details | STEAM TURBINE GENERATOR SET

6115-00-635-2570 A generator set using a steam turbine as the prime mover.

Part Alternates: 1JJ159, 6115-00-635-2570, 00-635-2570, 6115006352570, 006352570

Electric Wire, and Power and Distribution Equipment | Generators and Generator Sets, Electrical

Supply Group (FSG) NSN Assign. NIIN
61 00-635-2570

Request a Quote

What Our Customers Say

Compare

NSNs for Compare ( up to 4 ): Add 6115-00-635-2570

Technical Data | NSN 6115-00-635-2570

Characteristic Specifications
CURRENT TYPE AC
AC WATTAGE RATING 1500.0 KILOWATTS
FREQUENCY RATING 60.0 HERTZ NOMINAL
PHASE THREE
LINE TO LINE VOLTAGE IN VOLTS 450.0
POWER FACTOR IN PERCENT 0.8
EXCITOR TYPE SEPARATELY EXCITED
EXCITOR INCLUDED
AMBIENT TEMP IN DEG CELSIUS 50.0
TEMP RISE RATING IN DEG CELSIUS FOR CONTINUOUS OPERATION 70.0
MANUFACTURER NAME WESTINGHOUSE ELECTRIC CORP
IDENTIFYING NUMBER 1JH2801 DRAWING NO.
PRIME MOVER MANUFACTURER NAME WESTINGHOUSE ELECTRIC CORP
PRIME MOVER IDENTIFYING NUMBER 1JH2839 DRAWING NO.
STEAM OPERATING PRESSURE 1050.0 POUNDS PER SQUARE INCH GAGE
STEAM TEMP RATING 940.0 DEG FAHRENHEIT
TURBINE DESIGN TYPE IMPULSE
EXHAUST TYPE CONDENSING
STAGE TYPE MULTIPLE
TURBINE TO GENERATOR COUPLING METHOD GEAR TRAIN
MOUNTING TYPE BASE
OVERALL LENGTH 140.375 INCHES NOMINAL
OVERALL WIDTH 69.000 INCHES NOMINAL
OVERALL HEIGHT 162.500 INCHES NOMINAL
ACCESSORY COMPONENT QUANTITY 1 AND 1 AND 1 AND 1 AND 1
ACCESSORY CONTROLLING AGENCY WESTINGHOUSE ELECTRIC CORP,WESTINGHOUSE ELECTRIC CORP,WESTINGHOUSE ELECTRIC CORP,WESTINGHOUSE ELECTRIC CORP,GN
ACCESSORY COMPONENT NAME AIR EJECTOR,CONDENSER,GENERATOR,EXCIT ER,VOLTAGE REGULATOR,TURBINE AND GEAR ACCESSORIES
ACCESSORY IDENTIFYING NUMBER 1JH1388 DRAWING NO. AND 1JH1388 DRAWING NO. AND 1JH1815 DRAWING NO. AND 1JH1815 DRAWING NO. AND S17G74645-6260-004 PART NO.
III MAXIMUM WEIGHT CAPACITY 42.140 POUNDS
MANUFACTURERS CODE 79500
DESIGN CONTROL REFERENCE 1JJ159

Restrictions/Controls & Freight Information | NSN 6115-00-635-2570

Category Code Description
Hazardous Material Indicator CodeNThere is no data in the HMIS and the NSN is in an FSC not generally suspected of containing hazardous materials
Category Code Description
No Freight Information